Contact
    fix6.png
    Home > Product > CO2 Sensor
    High Accuracy NDIR CO2 Sensor CM1106HA-NS-1.png

    High Accuracy NDIR CO2 Sensor
    CM1106HA-NSCM1106HA-NS

    High accuracy with ±75ppm@400-2500ppm to meet newest AHSRAE 62.1-2022 standard for demand control ventilation(DCV) applications, CO2 sensor CM1106HA-NS can be used to detect CO2 concentration of indoor air by adopting advanced non-dispersive infrared technology (NDIR). With auto-calibration, no need of maintenance. It is widely used in ventilation system, HVAC, air conditioner, air purifier, IAQ monitor, agriculture, plant cultivation and cold-chain, etc.
    Show More

    Features


    • NDIR technology with independent intellectual property
    • Temperature calibration within whole measurement range
    • Long life span, auto-calibration, maintenance free
    • Small size and compact structure, easy to install



    Specifications

    CO2 Sensor CM1106-C
    Measurement range PWM: 0-2000ppm
    UART/ I²C: 0-10000ppm (Note 1)
    Working temperature -10°C ~ 50°C
    Working humidity 0-95%RH (non-condensing)
    Storage temperature -30°C ~ 70°C
    Storage humidity 0-95%RH (non-condensing)
    Accuracy ±75ppm@400-2500ppm, normal temperature and pressure. (Note 2 and 3)
    Sampling frequency 1s
    Response time ≤ 30s
    Power supply DC 4.5V~5.5V
    Ripple wave <50mV
    Working current <50mA
    Dimensions 33x19.7x8.9mm (pin is not included)
    Weight 5g
    Signal output UART_TTL /I²C/PWM
    Lifespan ≥15 years
    Maintenance Maintenance-free for normal indoor application with Auto-calibration
    Note 1:Sensor is designed to measure in the range 0~2000ppm (PWM),0-10000ppm (UART_TTL/I²C) with specified in the table accuracy. Nevertheless exposure to concentrations below 400ppm may result in incorrect operation of ABC algorithm and shall be avoided for model with ABC ON.
    Note 2:  In normal IAQ applications, accuracy is defined after minimum three (3) ABC periods of continuous
    operation with ABC on. Some industrial applications do require maintenance. Contact Cubic for further information
    Note 3: Specification is referenced to certified calibration mixtures. Uncertainty of calibration gas mixtures (±2% currently) is to be added to the specified accuracy for absolute measurement.
    * The above features and specifications are preliminary version. Some contents might be changed before the product is mass-production.
    To get more technical information, please contact info@.